Control Page
Internet Managed Thermostat Configuration Guide, Release 1.0 2-3
Part No. 600-03001-550, Rev. 1
Use Table 2-1 to configure the Control - HVAC fields.
Table 2-1 Control - HVAC Field Descriptions
Field Description
Temperature
Zone Temperature Displays the current temperature of the zone if temperature averaging is
disabled.
Average temperature of any combination of Local, Remote Sensor #1 (RS
#1), Remote Sensor #2 (RS #2), or Remote Sensor #3 (RS# 3) if
temperature averaging is enabled. (See Advanced Page (page 2-27).)
In a range of -30
°
F(-34
°
C) to 199
°
F(95
°
C)
Also displays the current status of the Zone Temperature alarm. If an alarm
occurs, you must repair the condition which caused the alarm before
resetting the alarm. (See Alarms Page (page 2-20).)
This field is blank if no Zone Temperature alarm exists.
Low Temperature Alert! – The temperature monitored within the
thermostat has dropped below the pre-set temperature threshold.
High Temperature Alert! – The temperature monitored within the
thermostat has risen above the pre-set temperature threshold.
Local Temperature Displays the current temperature of the local sensor. This field is disabled if
the local thermostat sensor is not included in temperature averaging.
In a range of 40
°
F(4.5
°
C) to 110
°
F(43.5
°
C)
Zone Humidity Displays the current Zone Humidity.
In a range of 0% to 95%
Low Humidity Alert! – The humidity level monitored within the
thermostat has dropped below the pre-set humidity threshold.
High Humidity Alert! – The humidity level monitored within the
thermostat has risen above the pre-set humidity threshold.
Heat Setting Displays the current temperature programmed for the heating system. This
field is disabled if the HVAC mode is set to Cool or Off. (See HVAC Mode
(page 2-5).) This field is not visible if the thermostat is configured to be a
cool-only controlling device. (See Advanced Page (page 2-27).)
To modify this field, use the drop-down menu to select a Heat Setting.
40
°
F(4.5
°
C) to 110
°
F(43.5
°
C)
Cool Setting Displays the current temperature programmed for the cooling (A/C) system.
This field is disabled if the HVAC mode is set to Heat or Off. (See HVAC
Mode (page 2-5).) This field is not visible if the thermostat is configured to
be a heat-only controlling device. (See Advanced Page (page 2-27).)
To modify this field, use the drop-down menu to select a Cool Setting.
40
°
F(4.5
°
C) to 110
°
F(43.5
°
C)