CHAPTER 2: Configuring the Thermostat Using the Web Interface
Use Table 2-6 to configure the Alarms - Wired Sensors page fields.
Table 2-6 Alarms - Wired Sensors Field Descriptions
Field Description
RS1:, RS2:, and RS3:
Low Temperature Limit Select a value or Disabled to indicate the low temperature
threshold detection status.
The value set by this parameter is monitored by the thermostat
and compared against the current Zone Temperature. If the
current Zone Temperature falls below this value, an alarm
condition is set and the status is displayed on the HVAC (page
2-2) page. In addition, this alarm is sent to the Proliphix web site
to trigger an e-mail notification, if the function is enabled, and
may also be sent as e-mail from this thermostat if configured on
Network: Notification Settings page. See E-mail configuration
on Network Notification Settings (page 2-42).
Disabled (default) – No low temperature limit is set.
-30
°
F(-34.5
°
C) to 200
°
F(93
°
C)
This is a major (red) alarm condition.
Present for Enter how long the condition must be in effect before the alarm
is triggered. Note that the default is 0 minutes and the maximum
time allowed is 240 minutes.
Alarm generated at The time the the alarm was generated.
High Temperature Limit Select a value or Disabled to indicate the high temperature
threshold detection status.
The value set by this parameter is monitored by the thermostat
and compared against the current Zone Temperature. If the
current Zone Temperature rises above this value, an alarm
condition is set and the status is displayed on the HVAC (page
2-2) page. In addition, this alarm is sent to the Proliphix web site
to trigger an e-mail notification, if the function is enabled, and
may also be sent as e-mail from this thermostat if configured on
Network: Notification Settings page. See E-mail configuration
on Network Notification Settings (page 2-42).
Disabled (default) – No high temperature limit is set.
-30
°
F(-34.5
°
C) to 200
°
F(93
°
C)
This is a major (red) alarm condition.
Present for Enter how long the condition must be in effect before the alarm
is triggered. Note that the default is 0 minutes and the maximum
time allowed is 240 minutes.