2-22 Internet Managed Thermostat Configuration Guide, Release 1.0
Part No. 600-03001-550, Rev. 1
CHAPTER 2: Configuring the Thermostat Using the Web Interface
Zone Humidity Alarms
Low Humidity Limit Select a value or Disabled to indicate the low humidity threshold
detection status.
This value is monitored by the thermostat and compared against
the current Relative Humidity. If the current Relative
Humidity rises above this value, an alarm condition is set and
the status is displayed on the HVAC (page 2-2) page. In
addition, this alarm is sent to the Proliphix web site to trigger an
e-mail notification, if the function is enabled, and may also be
sent as e-mail from this thermostat if configured on Network -
Notification Settings page. See E-mail configuration on
Network Notification Settings (page 2-42).
Disabled (default) – No high humidity limit is set.
0%RH to 95%RH – High Humidity Limit in 5%
increments.
This is a major (red) alarm condition.
High Humidity Limit Select a value or Disabled to indicate the high humidity
threshold detection status.
This value is monitored by the thermostat and compared against
the current Relative Humidity. If the current Relative
Humidity rises above this value, an alarm condition is set and
the status is displayed on the HVAC (page 2-2) page. In
addition, this alarm is sent to the Proliphix web site to trigger an
e-mail notification, if the function is enabled, and may also be
sent as e-mail from this thermostat if configured on Network -
Notification Settings page. See E-mail configuration on
Network Notification Settings (page 2-42).
Disabled (default) – No high humidity limit is set.
0%RH to 95%RH – High Humidity Limit in 5%
increments.
This is a major (red) alarm condition.
Filter Change Reminder
Change Interval (runtime hours) Select an interval in hours to remind you that the HVAC system
requires maintenance. This feature allows you to set time
intervals between changing and/or cleaning the HVAC air filter.
If enabled, an alarm condition is set after the pre-set interval has
expired, and is displayed on the HVAC (page 2-2) page. In
addition, this alarm is sent to the Proliphix web site to trigger an
e-mail notification, if the function is enabled, and may also be
sent as e-mail from this thermostat if configured on Network -
Notification Settings page. See E-mail configuration on
Network Notification Settings (page 2-42).
This is a minor (yellow) alarm condition.
Table 2-5 Alarms - Zone Field Descriptions (Continued)
Field Description