Register Designation Type Display / purpose
Bit 10 - INVALID METERING PARAMETER
ERROR
Bit 11 - OVERPRESSURE ERROR
Bit 12 - OVERCURRENT ERROR
Bit 13 - UNDERVOLTAGE ERROR
Bit 14 - AIR IN THE HEAD ERROR
Bit 15 - BLEEDING UNSUCCESSFUL ERROR
Bit 16 - OVERFLOW BATCH MEMORY ERROR
Bit 17 - INPUT CURRENT SMALLER THAN LIMIT
VALUE ERROR
Bit 18 - INPUT CURRENT LARGER THAN LIMIT
VALUE ERROR
Bit 19 - NEGATIVE PRESSURE ERROR
Bit 20 - NO "PUMP<->MODULE" CONNECTION
ERROR (not relevant for Modbus)
Bit 21 - NO "PUMP<-> MASTER" CONNECTION
ERROR (not relevant for Modbus)
Bit 22 - INTERNAL CAN-BUS ERROR (Only for
GXLa, Sigma, peristaltic pump,..)
Bit 23 - FAN ERROR
Bits 24 - 31 - RESERVED
1004 Error flags (2nd register) UINT32 Bits 0 - 31 - RESERVED
1006 Warning flags UINT32 Bit 0 - LEVEL WARNING
Bit 1 - DIAPHRAGM RUPTURE WARNING
Bit 2 - METERING MONITOR WARNING
Bit 3 - METERING VOLUME WARNING
Bit 4 - INVALID METERING PARAMETER
WARNING
Bit 5 - FAN WARNING
Bit 6 - WRONG MAGNET WARNING
Bit 7 - AIR IN DOSING HEAD WARNING
Bit 8 - OVERPRESSURE WARNING
Bit 9 - CAPACITY TOO LOW WARNING
Bit 10 - NEGATIVE PRESSURE WARNING
Bit 11 - CAVITATION WARNING
Bit 12 - POWER UNIT WARNING
Bit 13 - MODULE WARNING
Bits 14 - 31 - RESERVED
1018 Actual capacity FLOAT32 Dependent on - dosing head fitted - device context
(e.g. set suction stroke) - …
1020 Maximum possible capacity FLOAT32 Determined by - dosing head fitting - device context
(e.g. set suction stroke) - …
Supplementary operating instructions for Modbus RTU
38