Stop PROFINET
®
: The pump has been stopped using PRO‐
FINET
®
. The master has sent the pump a corresponding telegram.
Stop manual: The pump has been stopped using the
[Start/Stop]
key. The master has sent the pump a corresponding
telegram.
Connection error: If the pump loses its connection to the PRO‐
FINET
®
(as soon as the BUS cable is removed, the bus master is
switched to “Stop” status or the bus master becomes inoperative,
for example), then the
error symbol and the symbol appear.
Error module: If the pump loses its connection to the BUS
module (as soon as the BUS module is removed or if communica‐
tion between the BUS module and pump is interrupted for other
reasons, for example), the error symbol and the symbol
appear.
4.3.3
LEDs on the PROFINET
®
module
Signal Cause
Off The module has no supply voltage or connection.
Green The module and the master are exchanging information.
Green flashing The module has been initialised.
Signal Cause
Off The module has not been initialised.
Green The module has been initialised / normal mode
Green flashing, single flash The module has been initialised and there are diagnostic mes‐
sages.
Green flashing, 1 Hz DCP flash
Red Serious exception error
Red, single flash Configuration error
Red, double flash IP address error
Red, triple flash Station name error
Red, quadruple flash Internal error
4.3.4 Using the metering monitor
The "Metering monitor" socket must be used to use the metering
monitor in PROFINET
®
mode. The pump then transmits
‘available’
for the "Flow" status bit. The metering monitor can be switched on
and off using the PROFINET
®
by means of the
‘Metering monitor’
and/or
‘FlowControl’
parameters.
LED 1 (left) - module operating status
LED 2 (right) - module status
Supplementary Operating Instructions for PROFINET
®