The PROFIBUS
®
address must always be entered as 3 digits
(addresses from "002" to "125"):
1. 1. option: Turn the
[Clickwheel]
until the desired value is
reached and then press the
[Clickwheel]
.
2.
2. option: Press the
[Priming]
key to change to digit-by-
digit setting. Set the number using the
[Clickwheel]
and save
using the
[Priming]
key. The cursor moves to the next
number, and so on .
3.3
Special features in active PROFIBUS
®
operation
3.3.1 General
The pump cannot be manually set or programmed
in PROFIBUS
®
operation! To do this, set the PRO‐
FIBUS
®
to ‘Inactive’ .
n Using the
[Clickwheel]
it is possible to switch between the con‐
tinuous displays at any time, as in the other operating modes.
This does not affect the operation of the pump.
n When PROFIBUS
®
operation is selected, the settings from the
last operating mode without PROFIBUS
®
are applied. How‐
ever, settings made using the PROFIBUS
®
are not saved! They
only apply as long as the pump is linked to the PROFIBUS
®
.
Only the
‘stroke counter’
(total number of strokes) and the
‘quantity counter’
(total number of litres) continue to be
counted and saved.
n If the pump is set to PROFIBUS
®
operation, it stops. It can be
activated again by pressing the
[Stop/Start]
key. Use the
BUS to give the Start command.
3.3.2 Displays
There are additional identifiers in the operating display when PRO‐
FIBUS
®
operation is running.
The commonly used identifiers can be found in the
"Control elements" chapter in the "Peristaltic
metering pump DULCO flex Control, DFXa".
PROFI
BUS
Stop PROFIBUS
®
: The pump has been stopped using PRO‐
FIBUS
®
. The master has sent the pump a corresponding telegram.
Stop manual: The pump has been stopped using the
[Start/Stop]
key. The master has sent the pump a corresponding
telegram.
Connection error: If the pump loses its connection to the PRO‐
FIBUS
®
(as soon as the BUS cable is removed or the bus master
becomes inoperative, for example), the
error symbol and the
symbol appear.
Supplementary operating instructions for PROFIBUS
®
48

Table of Contents

Other manuals for ProMinent DULCO flex Control

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ProMinent DULCO flex Control and is the answer not in the manual?

ProMinent DULCO flex Control Specifications

General IconGeneral
BrandProMinent
ModelDULCO flex Control
CategoryWater Pump
LanguageEnglish

Related product manuals