Register Designation Type Display / purpose
1429 "Adaptive contact control"
contact input
Enum With adaptive contact control (exclusively in contact
mode), the stroke rate or capacity is set according to
the time interval of the incoming contact impulses. If
the time interval changes, the values mentioned
change adaptively.
0 - INACTIVE
1 - ACTIVE
1438 "Mass density feed chemical"
concentration mode
FLOAT32 Material characteristic of the feed chemical
0.5 … 2.0 kg/l
1440 "Flow main medium" concen‐
tration mode
FLOAT32 Characterised quantity of the main medium in which
metering is to be performed
0.1 … 9999.9 m
3
/h
1442 "Volumetric flow for max.
analogue value" concentra‐
tion mode
FLOAT32 Characterised quantity of the main medium in which
metering is to be performed
0.1 … 9999.9 m
3
/h
1444 "Volume main medium" con‐
centration mode
FLOAT32 Characterised quantity of the main medium in which
metering is to be performed
0.1 … 9999.9 l
1446 "Volume per contact
detected" concentration
mode
FLOAT32 Characterised quantity of the main medium in which
metering is to be performed
0.1 … 999.99 l / contact
2.10.8 "Accessories 1" register
These register inputs are all for function code "0x03", "0x06", 0x10
and 0x17 (Read / Write).
Register Designation Type Display / purpose
2000 Hose rupture sensor BOO‐
LEAN
Configuration as to how the pump should react to a
"hose rupture" event:
0 - WARNING
1 - ERROR
2.10.9 "Accessories 3" register
These register inputs are all for function code "0x03", "0x06", 0x10
and 0x17 (Read / Write).
Supplementary operating instructions for Modbus RTU
43