Register Designation Type Display / purpose
1200 Start/stop pump UINT8 Bit 0 - Start/Stop via bus
(0=PUMP STOPS; 1=PUMP ACTIVE OR IN
STANDBY)
Bit 1 - Start/Stop via Modbus-TimeOut
(0=no TimeOut; 1=TimeOut)
1211 Target capacity FLOAT32 Dependent on
- dosing head fitted
- device context (e.g. set suction stroke)
- …
1215 Metering volume per batch
mode triggered
FLOAT32 Specification for batch mode value range:
min. value is derived from the dosing head,
the max. value is also from the metering time set
1217 Metering time for batch UINT16 Min/max values are also controlled by specifying the
"Metering time for batch"
1 … 10,000 sec
1221 Metering volume per contact
mode triggered
FLOAT32 Specification for contact mode
0.00 001 … 99.99 l / Contact
1223 Auxiliary capacity FLOAT32 Dependent on
- dosing head fitted
- device context (e.g. set suction stroke)
- …
1225 Activate concentration mode BOOLEAN 0 - INACTIVE
1 - ACTIVE
1226 "Desired final concentration"
concentration mode
FLOAT32 0.01 … 100 000 ppm
1229 Target operating mode Enum 0 - EXTERNAL STOP
1 - MANUAL
2 - CONTACT
3 - BATCH
4 - ANALOGUE
1233 Priming duration UINT16 1 … 60 sec
1234 Clear counter Enum 0 - CLEAR STROKE COUNTER
1 - CLEAR QUANTITY COUNTER
2 - CLEAR CONTACT MEMORY
3 - CLEAR ALL COUNTERS
1235 Trigger a batch/contact cycle UINT16 When a Modbus message with this register number
and user data pattern "0x5555" is received,
depending on the operating mode set, a batch or
contact cycle is triggered
1236 Delete error requiring
acknowledgement
UINT16 When a Modbus message with this register number
and user data pattern "0x5555" is received, all errors
requiring acknowledgement are reset
Supplementary operating instructions for Modbus RTU
40