EasyManua.ls Logo

Ramtech WES3 - Initial Base Station Setup; Inspection Delay; Pre Alarm Mode

Ramtech WES3
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 26 WES
3
Installation and Operations Manual V2.0 Ramtech Electronics Limited 2020
b
1. Initial Base Station Setup
To activate the WES
3
Base Station, hold down ‘A and press ‘B’ three
timesinquicksuccession.AllthreeLEDswillbrieyilluminateandthen
theamberLEDwillash.
Initial setup of the Base Station is through a series of on-screen
options such as Language, Inspection Delay and Pre-Alarm mode
options.
Language Selection
Select language, available options are English, German, French,
Spanish, Italian and Swedish. Language settings can be changed at
any time via the menus within the Base Station.
SELECT LANGUAGE
> English
Deutsch
Français
Inspection Delay
The Inspection Delay setting allows an optional delay period between
triggering a call point and the site wide alarm being raised. This can
allow time for the incident to be validated on site, and a decision to be
made to either
i)conrmalarmisgenuine,raisesitewidealarmand
evacuate site, or
ii)conrmfalseactivation,cancelthealarmandreturnto
normal (non-alarm) state.
First time setup
Inspection delay
00 mins
Default setting is 00 minutes (ie no delay), but can be set in 1 minute
incrementsuptoamaximum10minutes.Aconrmationscreenwillbe
displayed to validate the setting and prevent accidental activation.
Basic System Setup (Base Station
version, if applicable to your system)
Alarm delay selected
This will increase
the time to activate
site alarm! Ok? Yes
Note that Inspection Delay can only be set during the initial
activation process. Once set, the Inspection Delay can only be
changed by turning off and reactivating the Base Station. This will
clear any existing unit numbering and other network settings from the
network.
Inspection delay
set to
02 minutes
Pre Alarm Mode
ThePreAlarmfunctiondenessite-widebehaviourofthenetwork
during an Inspection Delay period.
With Pre Alarm mode enabled, the entire network will emit a site-wide,
intermittent sound and (on strobe-equipped call points) an intermittent
ash,toalertsitepersonnelthatapotentialevacuationmaybe
imminent.
With Pre Alarm mode disabled, the local call point which has been
triggered will sound in addition to the CONNECT unit. All other call
points around site will remain in the normal state of non-alarm.
Enable Prealarm?
Yes
Note that Pre Alarm can only be set during the initial network
setup process. Once set, the Pre Alarm setting can only be changed
by turning off and reactivating the Base Station. This will clear any
existing unit numbering and other network settings from the network.

Table of Contents

Other manuals for Ramtech WES3

Related product manuals