EasyManua.ls Logo

Regency 4720 - Current Draw on Protective Devices Indicated by Leds 2 and 3 (F2 and F3)

Regency 4720
100 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Regency
®
Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A) Revised 10/98
21
4.1.2 Current Draw on Protective Devices Indicated by LEDs 2 and 3 (F2 and F3)
Calculate the alarm current drain on the protective devices indicated by LED 2 (F2) and LED 3 (F3).
First complete the calculations in Table 4.1.1.0a on the previous pages. Then use Table 4.1.2a to
perform the following calculations:
1. Write the Total alarm current (from Table 4.1.1.0a) in Column 3.
2. If there are any additional devices that are not associated with LED 2 or LED 3 (F2 or F3), write
them in the space provided, and write their current draws in Column 2.
3. Add Column 2. Write the total in Column 3 on the line labeled Alarm current NOT associated
with LED 2 or 3 (F2 or F3).
Model 7181 Univer-
sal Zone Con-
verter
5 F3 (1 per zone max.)
(See the Model 7
181 Installa-
tion Manual
P/N 150632,
in the electrical specifica-
tions sectionfor current
draw information. Be sure to
take the appropriate infor-
mation for the configuration
in which you’ve wired the
Model 7181.)
Wheelock Bell
2F2
3 max.)
× Standby: 0 mA = 0 mA
× Alarm: 125 mA = mA
8-ohm Speaker
2F2
(1 max.)
× Standby: 0 mA = mA
× Alarm: 750 mA = mA
45-ohm Speaker
2F2
(6 max.)
× Standby: 0 mA = mA
× Alarm: 133 mA = mA
Siren (15-watt
speaker)
1F1
(1 max.
× Standby: 0 mA = mA
× Alarm: 133 mA = mA
Zone Input
(16 max.)
× Standby: 0.6 mA = mA
Additional devices not listed above
× Standby: ____ mA = mA
× Alarm: ____ mA = mA
× Standby: ____ mA = mA
× Alarm: ____ mA = mA
× Standby: ____ mA = mA
× Alarm: ____ mA = mA
Total current ratings of all devices in system
mA
Standby
mA
Alarm
Table 4.1.1.0a: Current Load Worksheet
Device LED
(Revision
L
& Later)
Fuse #
(Prev.
Revs.)
# of Devices
(Max. Allowed)
Times Current Per
Device
*2
= Total
Standby
Current
Total
Alarm
Current
* Note 1: If no LED or fuse is shown, the accessory is resistively current limited.
* Note 2: Not UL = Not investigated by UL.
* Note 4: Not Ul = The maximum number shown for smoke detectors is for the entire installation (NOT per zone).

Table of Contents