6-28 Electrical Data Rexroth IndraDrive M
DOK-INDRV*-HMS+HMD****-PR04-EN-P
Control Voltage (+24 V, 0 V)
The control voltage supply is connected by contact rails and screws (M6)
to the front of the drive controller (cross section of a contact rail:
6 x 12 mm). There are various lengths of contact rail depending on the
width of the drive controllers. The contact rails are part of the accessories
HAS01.1.
6 Nm
DC Bus (L+, L-)
The DC bus is connected by contact rails and screws (M6) to the front of
the drive controller (cross section of a contact rail: 6 x 12 mm). There are
various lengths of contact rail depending on the width of the drive
controllers. The contact rails are part of the accessories HAS01.1.
6 Nm
X1, Bus Module
X1f2.FH7
X1 out X1 in
Fig. 6-25: X1
Type Number of
poles
Type of design
Flat line connector 8 Connector on device
Flat line bushing 8 Bushing on flat line
Fig. 6-26: Design
Design
Tightening Torque
Design
Tightening Torque
Graphic Representation
Design