39 • Chapter 3: Operation GX-3R Pro Operator’s Manual
Responding to Alarms
This section describes response to gas, over range, battery, sensor failure, LIMITED HC GAS
LIST, clock failure, system failure, man down, and panic alarms.
Responding to Gas Alarms
1. Determine which gas alarm has been activated.
2. Follow your established procedure for an increasing gas condition or a decreasing oxygen
condition.
3. Reset the alarm as necessary or allowed.
a. If LATCHING is set to ON (factory setting) in Maintenance Mode, the gas reading must
fall below (or rise above for an oxygen low alarm) an alarm setting before you can reset
the alarm condition using POWER MODE or AIR.
b. If Password Protection is turned On (factory setting is Off) using the SDM-3R PC
program, you must press POWER MODE and AIR at the same time and then enter a user-
set password to reset an alarm condition. When the password screen appears, adjust each
digit with the AIR button and press and release the POWER MODE button to move on to
the next digit. Once the password is entered, the alarm condition resets.
Man Down Alarm
The ALARM TIME defined in User
Mode has passed since the instru-
ment detected movement.
• MAN DOWN appears at the
bottom of the LCD and the gas
readings disappear
• Alarm LEDs flash in circle
sequence twice per second
• Backlight turns on
• High-low tone sounding
twice per second
• Vibrator pulses twice
per second
Panic
User double taps the
instrument.
Pre
Alarm
• Screen unaffected for 5 seconds
• Alarm LEDs flash twice per
second
• Single pulsing tone
twice per second for 5
seconds
Main
Alarm
• PANIC appears at the bottom of
the LCD and the gas readings
disappear
• Alarm LEDs flash in circle
sequence twice per second
• Backlight turns on
• High-low tone sounding
twice per second
• Vibrator pulses twice
per second
Alarm Type Visual Indications Other Indications