Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020 67
Kinetix and PowerFlex Drive Specifications Appendix A
D022 2
15 – 23.3 15.1
1020
40
Mersen HSJ40
(3)
11
– 10 14.7 9.5 30
Mersen HSJ30
(3)
D027 3
20 – 28.9 18.8
1200
50
Mersen HSJ50
(3)
11
–1523.315.1 40
Mersen HSJ40
(3)
D034 3
25 – 36.4 23.6
1500
60
Mersen HSJ60
(3)
11
–2028.918.8 50
Mersen HSJ50
(3)
D040 3
30 – 42.9 27.8
1800
80
Mersen HSJ80
(3)
11
–2536.423.6 60
Mersen HSJ60
(3)
D052 4
40 – 55.7 36.1
2400
90
Mersen HSJ90
(3)
11
–3042.927.8 80
Mersen HSJ80
(3)
D065 4
50 – 69.7 45.1
3000
100
Mersen HSJ100
(3)
11
–4055.736.1 90
Mersen HSJ90
(3)
D065 5
50 – 69.7 45.3
3600
100
Mersen HSJ100
(3)
11
–4055.736.2 90
Mersen HSJ90
(3)
D077 5
60 – 84.5 54.7
3600
150
Mersen HSJ150
(3)
11
– 50 69.7 45.1 100
Mersen HSJ100
(3)
D096 5
75 – 105.3 68.3
4500
175
Mersen HSJ175
(3)
11
– 60 84.5 54.7 150
Mersen HSJ150
(3)
D096 6
75 – 105.3 68.4
4600
175
Mersen HSJ175
(3)
11
– 60 84.5 54.9 150
Mersen HSJ150
(3)
D125 6
100 – 137.1 88.9
4600
200
Mersen HSJ200
(3)
11
– 75 105.3 68.3 175
Mersen HSJ175
(3)
D156 6
125 – 171.2 110.9
9200
300
Mersen HSJ300
(3)
11
– 100 137.1 88.9 200
Mersen HSJ200
(3)
D186 6
150 – 204.1 132.2
9200
400
Mersen HSJ400
(3)
11
– 125 171.2 110.9 300
Mersen HSJ300
(3)
D248 6
200 – 272.1 176.3
9200
400
Mersen HSJ400
(3)
11
– 150 204.1 132.2 400
Mersen HSJ400
(3)
(1) Drive input type (position 5 of catalog number) = 1 (AC input with precharge, includes DC terminals) or 4 (DC input with precharge).
(2) See Fuse Certification and Test Data
on page 68 for fuse self-certification and test data for Bussmann 170M and JKS fuses that are recommended for the DC-bus fusing.
(3) A test program was developed to confirm that the HSJ (High Speed J) fuses meet or exceed the requirements set forth by Rockwell Automation for the fuses on the common DC-bus for all
Allen-Bradley architecture, component, and legacy drives. The criteria for acceptance was:
• 600V AC rectified, 810V DC average, fuses located at (+) and (-) leg. Short circuit test at 65 kA.
• Time constant minimum 3 milliseconds (maximum 15 milliseconds).
• No over-load protection required.
• Let-through must be less than rating of the conductors.
This testing is listed in UL file E2137 Vol2 Sec 31 page 1 and in CSA report 1662646.
Table 61 - 650V DC Input Fuses, Frames 1…6 (continued)
Drive Cat. No.
20F and 20G
(1)
Frame
Size
HP Rating DC Input Rating
Drive DC Bus
Capacitance
Non-time Delay Fuse
ND HD Amps kW Amps Fuse Cat. No.
Quantity
µF DC+ DC–