112 Rockwell Automation Publication D2-3518-4 - January 2020
Chapter 9 Parameter Descriptions
Enables a feature to save the present frequency reference value issued by the OIM
to drive memory on power loss. Value is restored to the OIM on power up. HIM
stands for Human Interface Module. It is another way of referring to the OIM.
Figure 43 - Save OIM Ref (192)
Enables/disables a feature to automatically load the present auto frequency
reference value into the OIM when Manual is selected. Allows smooth speed
transition from Auto to Manual.
HIM stands for Human Interface Module. It is another way of referring to the
OIM.
Unipolar = Drive receives unsigned reference (0...32767) and
direction command separately (from the DPI port). For
example, the direction keys on an OIM apply the
direction to the reference.
Bipolar = Drive receives signed reference (-32767...32767). In this
case, the direction keys have no effect.
Reverse Disable = Drive receives signed reference (-32767...32767);
however, regardless of the reference, the drive is not
permitted to reverse.
192
Save HIM Ref
Range: See Figure 43
Default: See Figure 43
Access: 1 Path: Utility > HIM Ref Config
See also:
193
Man Ref Preload
Range: 0 = Disabled
1 = Enabled
Default: 0 = Disabled
Access: 1 Path: Utility > HIM Ref Config
See also: 320...327, 361...366
xxx1xxxxxxxxxxxx
0011234567891112131415
1=Save
0=Do Not Save
x =Reserved
Bit #
Factory Default Bit Values
At Powr Down
Nibble 1Nibble 2Nibble 3Nibble 4