Rockwell Automation Publication D2-3518-4 - January 2020 121
Parameter Descriptions Chapter 9
Figure 52 - Dig Out Status (276) Frame 4
The hottest measured inverter IGBT module temperature is displayed as
x.x degrees C.
Accumulated percentage of drive overload. Continuously operating the drive
over 100% of its rating increases this value to 100% and causes a Drive OverLoad
fault (fault 64).
Accumulated percentage of motor overload. Continuously operating the motor
over 100% of Motor OL Amps (48) increases this value to 100% and causes a
Motor OverLoad fault (fault 7).
Displays the imbalance in current between motor phases.
If the imbalance count remains over inverter Imbalance Limit (49) for more than
inverter Imbalance Time (50), the Motor I Imbalance fault (fault 37) occurs.
218
Invtr Base Temp
Range: -/+100 °C [0.1 °C]
Default: Read Only
Access: 1 Path: Utility > Diagnostics
See also:
219
Drive OL Count
Range: 0.0...100.0% [0.1%]
Default: Read Only
Access: 1 Path: Utility > Diagnostics
See also: 150
220
Motor OL Count
Range: 0.0...100.0 [1.0%]
Default: Read Only
Access: 1 Path: Utility > Diagnostics
See also: 47, 48
221
Imbalance Count
Range: 0.0...100.0 [1.0%]
Default: Read Only
Access: 1 Path: Utility > Diagnostics
See also: 22...24, 49, 50
0xxxxx
0011234567891112131415
1 =Condition True
0=Condition False
x =Reserved
Bit #
Digital Output 1
Nibble 1Nibble 2Nibble 3Nibble 4
xxx
000
0
0
00
Digital Output 6
Digital Output 8
Digital Output 2
Digital Output 7
Digital Output 5
Digital Output 4
Digital Output 3