Chapter 9 Parameter Descriptions
Figure 50 - Dig In Status (216)
For Frame 3 drives (firmware version 1.x), this parameter is only usable if an
optional Standard I/O board is present.
This parameter contains the current state of digital outputs controlled by the
inverter. See AC Line I/O Board Description (Frame 3 Only)
on page 25
through Combined I/O Board Description (Frame 4 Only)
on page 29 for a
description of I/O hardware that is present on this drive and is controlled by the
inverter.
Frame 3 drives (firmware version 1.x) only:
Current state of the user-configurable digital outputs. These outputs are located
on the optional Standard I/O board, which is not present in all drives.
Figure 51 - Dig Out Status (276) Frame 3
Frame 4 drives (firmware version 2.x) only:
Current state of the inverter-controlled digital outputs.
Digital outputs 1 and 2 are the user-configurable digital outputs. Digital Outputs
3...8 are the application controlled digital outputs. All of these digital outputs are
located on the Combined I/O board.
217
Dig Out Status
Range: See Figure 51 and Figure 52
Default: Read Only
Access: 0 Path: Utility > Diagnostics
See also: 30, 380...384
000000xxxxxxxxxx
0011234567891112131415
1 =Input Active
0=Input Not Active
x =Reserved
Bit #
Digital In1
Digital In2
Digital In3
Digital In4
Digital In5
Digital In6
Nibble 1Nibble 2Nibble 3Nibble 4
0xx0xxxxxxxxxxxx
0011234567891112131415
1 =Output Energized
0=Output De-energized
x =Reserved
Bit #
Digital Out1
Digital Out2
Nibble 1Nibble 2Nibble 3Nibble 4