Rockwell Automation Publication D2-3518-4 - January 2020 119
Parameter Descriptions Chapter 9
Displays the drive conditions currently preventing the drive from starting.
Figure 49 - Start Inhibits (214)
Displays the source that initiated the most recent stop sequence. It is cleared (set
to 0) during the next start sequence.
For Frame 3 drives, this parameter provides the state of the user-configurable
Digital Inputs on the optional A22 Standard I/O board.
For Frame 4 drives, this parameter provides the state of the user-configurable
Digital Inputs on the A12 Combined I/O board.
See AC Line I/O Board Description (Frame 3 Only)
on page 25 through
Combined I/O Board Description (Frame 4 Only)
on page 29 for a description
of I/O hardware that is present on this drive and is controlled by the inverter.
215
Last Stop Source
Range: 0 = Pwr Removed
1 = DPI Port 1
2 = DPI Port 2
3 = DPI Port 3
4 = DPI Port 4
5 = DPI Port 5
6 = DPI Port 6 (Frame 4 only)
7 = Digital In
8 = Fault
9 = Not Enabled
10 = Sleep
11 = Jog
Default: Read Only
Access: 1 Path: Utility > Diagnostics
See also:
216
Dig In Status
Range: See Figure 50
Default: Read Only
Access: 0 Path: Utility > Diagnostics
See also: 361...366
0000000x0000000x
0011234567891112131415
1 =Inhibit True
0=Inhibit False
x=Reserved
Bit #
Fault
Type 2 Alarm
Enable
Rctfr NotRdy
DPI Stop
Params Reset
StartUp Actv
Digital In
DPI Port 1
DPI Port 2
DPI Port 3
DPI Port 4
DPI Port 5
DPI Port 6 (Frame 4)
Nibble 1Nibble 2Nibble 3Nibble 4