118 Rockwell Automation Publication D2-3518-4 - January 2020
Chapter 9 Parameter Descriptions
Indicates Type 2 alarm conditions that currently exist in the drive. See
Chapter 10
for more information about alarms.
Figure 48 - Drive Alarm 2 (212)
Displays the source of the speed reference of the drive.
212
Drive Alarm 2
Range: See Figure 48
Default: Read Only
Access: 1 Path: Utility > Diagnostics
Utility > Alarms
See also: 211
213
Speed Ref Source
Range: 0 = PI Output
1 = Analog In 1
2 = Analog In 2
3...8 = Reserved
9 = MOP Level
10 = Jog Speed
11 = Preset Spd 1
12 = Preset Spd 2
13 = Preset Spd 3
14 = Preset Spd 4
15 = Preset Spd 5
16 = Preset Spd 6
17 = Preset Spd 7
18 = DPI Port 1
19 = DPI Port 2
20 = DPI Port 3
21 = DPI Port 4
22 = DPI Port 5
23 = DPI Port 6 (Frame 4 only)
Default: Read Only
Access: 1 Path: Utility > Diagnostics
See also: 90, 93, 96, 101
214
Start Inhibits
Range: See Figure 49
Default: Read Only
Access: 0 Path: Utility > Diagnostics
See also:
0000000000000xxx
0011234567891112131415
1 =Alarm Active
0=Alarm Inactive
x =Reserved
Bit #
DigIn CflctA
DigIn CflctB
DigIn CflctC
Bipolr Cflct
MtrTyp Cflct
NP Hz Cflct
MaxFrq Cflct
VHz NegSlope
IR Vlts Rang
FlxAmps Rang
SpdRef Cflct
Ixo Volt Range
Sleep Config
Nibble 1Nibble 2Nibble 3Nibble 4