Rockwell Automation Publication D2-3518-4 - January 2020 155
Parameter Descriptions Chapter 9
Sets the user-configurable digital output activation level for options 10...15 in
Digital Out1 Sel. Units are assumed to match the above selection (for example,
At Freq = Hz, At Torque = Amps).
See AC Line I/O Board Description (Frame 3 Only)
on page 25 through
Combined I/O Board Description (Frame 4 Only)
on page 29 for a description
of I/O hardware that is present on this drive and is controlled by the inverter.
Sets the on delay time for user-configurable digital output 1. This is the time
between the occurrence of a condition and activation of the user-configurable
digital output.
See AC Line I/O Board Description (Frame 3 Only)
on page 25 through
Combined I/O Board Description (Frame 4 Only)
on page 29 for a description
of I/O hardware that is present on this drive and is controlled by the inverter.
Sets the off delay time for user-configurable digital output 1. This is the time
between the disappearance of a condition and de-activation of the user-
configurable digital output.
See AC Line I/O Board Description (Frame 3 Only)
on page 25 through
Combined I/O Board Description (Frame 4 Only)
on page 29 for a description
of I/O hardware that is present on this drive and is controlled by the inverter.
382
Dig Out1 OnTime
Range: 0.00...600.00 sec [0.01 sec]
Default: 0.00 sec
Access: 1 Path: Inputs & Outputs > Digital Outputs
See also: 380
383
Dig Out1 OffTime
Range: 0.00...600.00 sec [0.01 sec]
Default: 0.00 sec
Access: 1 Path: Inputs & Outputs > Digital Outputs
See also: 380