Rockwell Automation Publication D2-3518-4 - January 2020 77
Parameter Descriptions Chapter 9
Figure 32 - Rectifier Control (33) Frame 3
Frame 4 drives (firmware version 2.x) only:
Figure 33 - Rectifier Control (33) Frame 4
The actual state of the rectifier.
Frame 3 drives (firmware version 1.x) only:
34
Rctfr Status
Range: See Figure 34 and Figure 35
Default: N/A
Access: 1 Path: Monitor > Application
See also: rectifier 101
IMPORTANT This parameter is used for communication between the inverter and the
rectifier. Do not write to this parameter using VS Utilities, DriveExplorer, or an
OIM. Its value changes according to the operational state of the drive.
xxx
0011234567891112131415
x =Reserved
Bit #
AC Line I/O: Dig. Output 1
AC Line I/O: Dig. Output 2
AC Line I/O: Dig. Output 3
AC Line I/O: Dig. Output 4
AC Line I/O: Dig. Output 5
AC Line I/O: Dig. Output 6
Close Pre-charge
Enable Rectifier
Reset Recifier Fault
Inverter Fault
Network Loss
DC Bus Limit
Extend
Nibble 1Nibble 2Nibble 3Nibble 4
x
0011234567891112131415
x =Reserved
Bit #
Shunt Trip
Nibble 1Nibble 2Nibble 3Nibble 4
x
x
xx
xx
x
Enable Rectifier
Close Pre-charge
Reset Rectifier Fault
Inverter Fault
Network Loss
DC Bus Limit
Extend