Rockwell Automation Publication D2-3518-4 - January 2020 97
Parameter Descriptions Chapter 9
Selects the source of the PI reference signal.
Provides an internal fixed value for the process setpoint when PI Reference Sel
(126) is set to PI Setpoint.
126
PI Reference Sel
Range: 0 = PI Setpoint
1 = Analog In 1
2 = Analog In 2
3...8 = Reserved
9 = MOP Level
10 = Master Ref
11 = Preset Spd 1
12 = Preset Spd 2
13 = Preset Spd 3
14 = Preset Spd 4
15 = Preset Spd 5
16 = Preset Spd 6
17 = Preset Spd 7
18 = DPI Port 1
19 = DPI Port 2
20 = DPI Port 3
21 = DPI Port 4
22 = DPI Port 5
Default: 0 = PI Setpoint
Access: 1 Path: Speed Command > Process PI
See also: 124...138
127
PI Setpoint
Range: -/+100.00% of Maximum Process Value [0.01%]
Default: 50.00%
Access: 1 Path: Speed Command > Process PI
See also: 124...138