98 Rockwell Automation Publication D2-3518-4 - January 2020
Chapter 9 Parameter Descriptions
Selects the source of the PI feedback signal.
Specifies the time required for the integral component to reach 100% of PI Error
Meter (137).
Sets the value for the PI proportional component when the PI Hold bit of PI
Control (125) = Enabled (1).
PI Error x PI Prop Gain = PI Output
128
PI Feedback Sel
Range: 0 = PI Setpoint
1 = Analog In 1
2 = Analog In 2
3...8 = Reserved
9 = MOP Level
10 = Master Ref
11 = Preset Spd 1
12 = Preset Spd 2
13 = Preset Spd 3
14 = Preset Spd 4
15 = Preset Spd 5
16 = Preset Spd 6
17 = Preset Spd 7
18 = DPI Port 1
19 = DPI Port 2
20 = DPI Port 3
21 = DPI Port 4
22 = DPI Port 5
Default: 2 = Analog In 2
Access: 1 Path: Speed Command > Process PI
See also: 124...138
129
PI Integral Time
Range: 0.00...100.00 sec [0.01 sec]
Default: 2.00 sec
Access: 1 Path: Speed Command > Process PI
See also: 124...138
130
PI Prop Gain
Range: 0.00...100.00 [0.01]
Default: 1.00
Access: 1 Path: Speed Command > Process PI
See also: 124...138
131
PI Lower Limit
Range: -/+Maximum Frequency [0.1 Hz]
Default: -Maximum Freq
Access: 1 Path: Speed Command > Process PI
See also: 124...138