12-76
SP600 AC Drive User Manual
Selects parameter number whose value will be written from a
communications device data table. Refer to figure 12.47.
Parameters that can be changed only while the drive is stopped
cannot be used as Datalink inputs. Entering a parameter of this type
will disable the link.
Refer to the appropriate communications module manual for more
information about Datalinks.
Parameter number whose value will be written from a
communications device data table. Refer to figure 12.47.
Parameters that can be changed only while the drive is stopped
cannot be used as Datalink inputs. Entering a parameter of this type
will disable the link.
Refer to the appropriate communications module manual for more
information about Datalinks.
300
301
Data In A1 - Link A Word 1
Data In A2 - Link A Word 2
Range: 0 to 387 [1]
Default: 0 (Disabled)
Access: 2 Path: Communication>Datalinks
See also:
Figure 12.47 – Data Received By the Drive From the Network
302
303
Data In B1 - Link B Word 1
Data In B2 - Link B Word 2
Range: 0 to 387 [1]
Default: 0 (Disabled)
Access: 2 Path: Communication>Datalinks
See also:
Network
Module
P#
Data
SP600 Drive
Network
Data In
P(xx)