Reference Manual
00809-0100-4664, Rev BA
January 2010
Rosemount 8712
E-34
TAYLOR SENSORS Connect coil drive and electrode cables as shown in Figure E-32.
Series 1100 Sensor to
Rosemount 8712
Transmitter
Figure E-32. Wiring Diagram for
Taylor Series 1100 Sensors and
Rosemount 8712
Table E-30. Taylor Series 1100 Sensor Wiring Connections
Rosemount 8712 Taylor Series 1100 Sensors
1Black
2 White
Green
17 S1 and S2
18 E1
19 E2
1
2
17
18
19
ROSEMOUNT 8712
TRANSMITTER
Electrode Connections
Coil Connections
TAYLOR SERIES 1100
SENSOR
C
L
A
R
White
Black
Green
L N G 1 2 3 4
This is a pulsed DC magnetic flowmeter.
Do not connect AC power to the sensor
or to terminals 1 and 2 of the
transmitter, or replacement of the
electronics board will be necessary.