Reference Manual
00809-0100-4664, Rev BA
January 2010
Rosemount 8712
www.rosemount.com
Appendix C Diagnostics
Diagnostic Availability . . . . . . . . . . . . . . . . . . . . . . . . . . . . page C-1
Licensing and Enabling . . . . . . . . . . . . . . . . . . . . . . . . . . . page C-2
Tunable Empty Pipe Detection . . . . . . . . . . . . . . . . . . . . . page C-2
Ground/Wiring Fault Detection . . . . . . . . . . . . . . . . . . . . .page C-4
High Process Noise Detection . . . . . . . . . . . . . . . . . . . . . . page C-5
8714i Meter Verification . . . . . . . . . . . . . . . . . . . . . . . . . . . page C-8
Rosemount Magnetic Flowmeter
Calibration Verification Report . . . . . . . . . . . . . . . . . . . . . page C-16
DIAGNOSTIC
AVAILABILITY
Rosemount Magmeters provide device diagnostics that powers PlantWeb and
informs the user of abnormal situations throughout the life of the meter - from
installation to maintenance and meter verification. With Rosemount Magmeter
diagnostics enabled, users can change their practices to improve plant
availability and output, and reduce costs through simplified installation,
maintenance and troubleshooting.
Options for Accessing Diagnostics
Rosemount magmeter diagnostics can be accessed through the Local
Operator Interface (LOI), the 375 Handheld Communicator, and AMS Device
Manager.
Access Diagnostics through the LOI for quicker installation,
maintenance, and meter verification
Rosemount magmeter diagnostics are available through the LOI to make
maintenance of every magmeter easier.
Diagnostics Mag User Practice
8712
HART
Basic
Empty Pipe Process Management •
Electronics Temperature Maintenance •
Coil Fault Maintenance •
Transmitter Faults Maintenance •
Reverse Flow Process Management •
Advanced (Suite 1) DA1 Option
High Process Noise Process Management •
Grounding/Wiring Fault Installation •
Advanced (Suite 2) DA2 Option
8714i Meter Verification Calibration Verification •