Reference Manual
00809-0100-4664, Rev BA
January 2010
E-37
Rosemount 8712
YAMATAKE
HONEYWELL SENSORS
Connect coil drive and electrode cables as shown in Figure E-35.
Yamatake Honeywell
Sensor to
Rosemount 8712
Transmitter
Figure E-35. Generic Wiring
Diagram for Yamatake
Honeywell Sensors and
Rosemount 8712
Table E-33. Yamatake Honeywell Sensor Wiring Connections
Rosemount 8712 Yamatake Honeywell Sensors
1X
2 Y
Chassis Ground
17 C
18 B
19 A
Electrodes
Coils
Chassis Ground
ROSEMOUNT 8712
TRANSMITTER
YAMATAKE
HONEYWELL
SENSORS
Y
X
A
B
C
Fuse
This is a pulsed DC magnetic flowmeter.
Do not connect AC power to the sensor
or to terminals 1 and 2 of the
transmitter, or replacement of the
electronics board will be necessary.