Page 13 of 82 Revision No.: 1.5
4) Communicator Setting
Cold Start procedure is committed with every software change. Restoring old setting
is always recommended.
I) Initial Setup
1. Hardware Profile
Go to Menu 9.1 (see Fig. 3) that defines the Hardware Profile and check whether the
Communicator recognizes the hardware. If the communicator did not recognize all of
the connected hardware, please refer to Appendix A.
2. Local Network Setup
After making sure the Communicator's hardware is ok adapt the Communicator to
Rotem controllers by either hard wired 485/RS232 or RF.
Go to menu 1.2 (see Fig. 3) and set the next parameters:
Baud Rate: Set according to the controllers Baud rate. The recommended
rate is 9600.
Primary Units: Insert the number of master controllers, for example -
Platinum Plus.
Secondary Unit: Insert the number of slave controllers. Note that when
exiting this menu, the communicator will reset in order to save changes.
3. Regional Setting
Go to menu 2 (see Fig. 3) and fill in the correct clock time, date and region of the
communicator. The communicator will reset in order to build Network Objects.