Platinum Plus
31
Feed
The FEED menu can be programmed to correspond to the light table, or simply enter the first
line only to allow the control hopper to run the feed system.
Feed
Day Start End
1 00:00 00:00
Extra Systems
The EXTRA SYSTEMS are a set of 4 controls you can use for various purposes. Use Extra
System 1 for the Fail Safe system by programming it to be always on as shown. Then, in the
event of power failure or many other types of controller failure, this relay will activate the fail
safe backup.
Extra Systems
Parameter System 1 System 2 System 3 System 4
Start Time 00:00
End Time 00:00
From Temp 0
To Temp 122.0
From Humidity 0
To Humidity 100
On Seconds 1
Off Seconds 0
Static Pressure
The STATIC PRESSURE settings control air pressure in both side (or minimum) ventilation
and in tunnel ventilation. To view the optional parameters, press the Help key and then choose
the Set option.
Pressure
Side Tunnel
Low Pressure Setting 0.070 0.030
High Pressure Setting 0.100 0.100
Low Pressure Alarm 0.020 0.010
High Pressure Alarm 0.150 0.150
Help | Set Parameters
Wind Gust Delay Time (Sec) 20 Pressure During Tunnel? 1 (yes)
Transitional Tunnel ? 1 (yes) Min Vent Using Inlet/Tunnel? 0 (side inlet)
Emergency Pressure Delay (Sec) 60 Curtain Position in Emergency 100% open
Minimum Curtain Level in Tunnel 50 Min Tun Level, % for Fans 25%
Vent Motor, Fast/Slow? 1 (fast) Time to Produce Pressure 10 seconds