Use of Turnaround Delays
Some RTU protocols (such as ModBus) use the concept of a turnaround delay. When 
the host sends a message (such as a broadcast) that does not invoke an RTU response, 
it waits a turnaround delay time. This delay ensures that the RTU has time to process 
the broadcast message before it has to receive the next poll.
When polling is performed, network delays may cause the broadcast and next poll to 
arrive at the remote server at the same time. Configuring a turnaround delay will 
enforce a minimum separation time between each message sent out the port.  Note 
that turnaround delays do not need to be configured at the host computer side and may 
be disabled there.
TcpModBus Server Application
The TcpModbus Server application is used to transport Modbus requests and 
responses across IP networks.  
The source of the polls is a Modbus “master”, a host computer that issues the polls 
over a serial line. 
A TcpModbus Client application, such as that implemented by the RuggedServer 
accepts Modbus polls on a serial line from a master and determines the IP address of 
the corresponding RTU.  The client then encapsulates the message in TCP and 
forwards the frame to a Server Gateway or native TcpModbus RTU.  Returning 
responses are stripped of their TCP headers and issued to the master.
The TcpModbus Server application accepts TCP encapsulated modbus messages from 
Client Gateways and native masters.  After removing the TCP headers the messages 
are issued to the RTU.  Responses are TCP encapsulated and returned to the 
originator.
A “native” TcpModbus master is one that can encapsulate the Modbus polls in TCP 
and directly issue them to the network.
Local Routing At The Server Gateway
The Server Gateway supports up to 32 RTUs on any of its four ports.  When a request 
for a specific RTU arrives the server will route it to the correct port.
MultiMaster Capability
It is possible for multiple masters to simultaneously issue requests for the same RTU. 
The Server Gateway will queue the requests and deliver them to the RTU in turn. 
This “multimaster” capability allows widely distributed masters to configure and 
extract information from the RTU.
TcpModbus Concepts And Issues
Host And Remote Roles
Client gateways (such as that implemented by the RuggedRouter) always make the 
TCP connection to the Server Gateway.  The Server Gateway can only accept a 
connection.  