1st Edition of TEMP880S IM : Sep. 21. 2005 Page 62 / 101
2.12.4.2 PID GROUP(PID1~PID4) SETTING
Generally, it uses value calculated by Auto Tuning, but users can set manually as well.
Diagram 2-53. PID Group
No. Instruction Contents Additional Explanation
1
PROPORTIONAL
BAND
Sets proportional band.
▶ Lessens the different between setting
point(SP) and the pointing value
(PV).
☞ Large proportional band: PV
approaches to SP quickly, but
vibration of MV will affect adversely
upon safety of control Small
proportional band: PV approaches
to SP slowly, and remaining deviation
may occur.
2
INTEGRAL
TIME
Sets integral time.
▶ Expanding integral time: Control
Output(MV) is lessened. Therefore,
approaching time to setting point(SP)
is lengthened.
Shortening integral time: Control
Output(MV) is increased. Therefore,
approaching time to setting point is
shortened.
☞ Intergal operation can eliminate
remaining derivitation at program
operation.
☞ If integral time is too short, controlling
may become impossible.
3
DERIVATIVE
TIME
Sets derivative time.
It restraints PV-SP changing rate by
caculating MV which rises along PV-
SP changing rate.
☞ It restraints a radical change of PV or
disturbance and accerates the
approach to setting point(SP).
4
OUTPUT LIMIT
HIGH
Sets control output operation
range limit high.
5
OUTPUT LIMIT
LOW
Sets control output operation
range limit low.
OH > OL
1
2
3
4