1st Edition of TEMP880S IM : Sep. 21. 2005 Page 68 / 101
2.12.6.2 DI ERROR NAME SETTING
Diagram 2-62. DI Error Name Setting Screen
No. Instruction Contents Additional Explanation
1
BUZZER TIME Sets time for DI Error buzzer.
▶ Although it is set to“0”, alarm goes
off for at least one minute.
2
DI1
Using DI1, you can select
operation status (RUN / STOP ).
☞ Cannot amend.
3
DI2 ~ DI8
NAME SET
You can set DI error name up to
nine letters (English or number).
▶ Refer to 2.10.6.1 How To Set Pattern
Name for DI name setting.
4
NEXT BUTTON Moves to Alarm Setting Screen. ▶ Refer to 2.12.6.1 Alarm Setting
2.12.6.3 SCREEN DURING DI ERROR OCCURRENCE
Diagram 2-63. Screen During DI Error Occurrence
No. Instruction Contents Additional Explanation
1
EXIT BUTTON Exits error screen.
▶ Returns to Operation Screen.
☞ Displays error screen again if error is
not resolved.
2
STOP BUTTON Turns off alarm sound.
3
DI ERROR ON
Reverses lamp and name of DI
which has error.
▶ Displays red.
☞ It becomes green after error is
removed.
Operation stops if DI2~DI4 error occurs
It operates by DO CONFIG DI Mode when DI5~DI8 error occurs.