PY Manual Copyright © 2006 SANYO DENKI AMERICA, Inc.
93
High Speed
HTG
Remote Operator Mode:
1
Page:
6
Default Value:
1000 min
-1
Function:
Monitor
Setting Range:
0 to 32767 min
-1
Description:
• High speed: When the speed exceeds this set level the “high speed” (HTG) status is turned ON (CN1-39) if
enabled.
•
The LTG status can be output to CN1-39 or CN1-40 by setting Function Switch 4.
•
The following switching (control mode) enables a speed limit to be set in the torque control mode:
Velocity Torque
Position Torque
Speed Matching Width SPE
Remote Operator Mode:
1
Page:
7
Default Value:
50 min
-1
Function:
Setting Range:
0 to 32767 min
-1
Description:
• When the difference between the velocity command and the velocity feedback is smaller than the specified
value, the SPE status is turned on if enabled.
• The LTG status can be output to CN1-39 or CN1-40 by setting Function Switch 4.
Internal Velocity Command Value #1 VCI1
Remote Operator Mode:
1
Page:
8
Default Value:
500 min
-1
Function:
Setting Range:
0 to 32767 min
-1
Description:
• Sets a velocity command value.
•
It is enabled by setting the Func3 parameter bits 3, 2, 1, and 0 to “1010” respectively, and turn the CN1-36 pin
“ON” and CN1-35 pin “OFF”.
•
The drive must be configured for velocity mode operation.