Introduction 3
Setpoints
16 programmable setpoints for monitoring various events:
- up to 4 triggering conditions for each setpoint combined by OR/AND
logical operations
- up to 4 actions for each setpoint on setpoint operation
- programmable hysteresis (dead-band) for analog triggers
- programmable delay for setpoint operation/release
each setpoint can be combined with other setpoints if extended number of
conditions or actions needed
any measured or sensed quantity/status/pulse/event can be used as a trigger
condition for setpoint operation
voltage disturbance and phase rotation monitoring are available for triggering
setpoint operations
setpoint actions available:
- operating relay output
- increment/decrement/clear counter
- assert/clear user programmable event
- reset total accumulating energy registers
- reset extreme demand registers
- reset TOU system accumulating energy registers
- reset TOU system demand registers
- clear all counters
- clear Min/Max log registers
- event logging on setpoint operation
- data logging in selected data log partition
- high-speed waveform logging for disturbance analysis
- high-resolution waveform logging for harmonic analysis
each setpoint can be programmed to be operated manually via
communications by overriding present conditions or by gating setpoint
operations in addition to other setpoint conditions (for example when
event/data recording is needed for a user-defined time interval)
each setpoint can be programmed to allow the setpoint operations to be
recorded in the event log on any setpoint transition - operate, release or either
transition
On-board Data Recording
19 free-programmable extended memory partitions for recording events,
measured data, and captured waveforms:
- one event logging partition for recording various events and setpoint
operations, providing storage for up to 36864 events with a 512K
memory module (assuming the entire memory allocated for the
partition)

Table of Contents