110
Technical Specifications
Measurement Specifications
Parameter, unit Full scale Accuracy, % Range Resolution
@
range
Rdg FS Conditions Front panel display Comm.
Voltage, V
120V×PT
@ 120V
380V×PT
@ 660V
208V×PT
@ 120V
660V×PT
@ 660V
0.2
10% to 120%
FS
0 to 999,000 1 V
@
1 to 999 V
1%
@
1,000 to 999,000 V
1 V
Line current, A CT primary current 0.2
2% to 120%
FS
0 to 60,000 1 A
@
1 to 9,999 A
0.1%
@
10,000 to 60,000A
1 A
Active power, kW
0.36×PT×CT @ 120V input
1.14×PT×CT @ 660V input
0.5
|PF| 0.5
0 to
± 2,147,000
1 kW
@
1 to 99,999/-9.999
0.01%
@
100 to 2,147 MW
0.1%
@ -
10 to -2,147 MW
1 kW
Reactive power,
kvar
0.36×PT×CT @ 120V input
1.14×PT×CT @ 660V input
0.5
|PF| 0.9
0 to
± 2,147,000
1 kvar
@
1 to 99,999/-9.999
0.01%
@
100 to 2,147Mvar
0.1%
@ -
10 to -2,147 Mvar
1 kvar
Apparent power,
kVA
0.36×PT×CT @ 120V input
1.14×PT×CT @ 660V input
0.5
|PF| 0.5
0 to 2,147,000 1 kVA
@
1 to 9,999
0.1%
@
10 to 2,147 MVA
1 kVA
Power factor 1 1
|PF| 0.5
-0.99 to +1.00 0.01 0.01
Neutral current, A CT primary current 0.5
2% to 120%
FS
0 to 60,000 1 A
@
1 to 999 A
1%
@
1,000 to 60,000 A
1A
Auxiliary current,
mA/A
Auxiliary CT primary
current
1
2% to 120%
FS
0 to 60,000 1 mA/A
@
1 to 999 mA/A
1%
@
1,000 to 60,000
1 mA/A
For Ln reading
and for
3OP2/3OP3
wiring
modes
For LL reading
except
3OP2/3OP3
wiring modes
or
or