EasyManuals Logo

Satec System 295 User Manual

Default Icon
173 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #18 background imageLoading...
Page #18 background image
10
Introduction
NOTES
¬ For all applications/outputs, the voltage parameters can represent line-to-neutral or line-to-line voltages depending on the
wiring configuration selected in the Powermeter. (4Ln3/3Ln3 = line-to-neutral voltages; all other configurations = line-to-line
voltages).
- In 3-wire connection schemes, the individual phase values for power factor, active power, apparent power and reactive power
will be zero, because they have no meaning. Only total three-phase power values can be used.
® In all grounded connections using either 4Ln3 or 4LL3 wiring configurations, harmonic voltages will represent line-to-neutral
voltages. In a 3-wire direct connection, harmonic voltages will represent line-to-neutral voltages that arise on the Powermeter's
input transformers. In a 3-wire open delta connection, harmonic voltages will comprise L12 and L23 line-to-line voltages.
¯ Display readings are the maximum demands over entire time of survey.
° Measurements can be made via 16 programmable Min/Max registers.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Satec System 295 and is the answer not in the manual?

Satec System 295 Specifications

General IconGeneral
BrandSatec
ModelSystem 295
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals