Back-up to perform GS 1 Rental application Stop Faults Alarms
A612: Single Genset without N/E
Validation
Mains supply detection using the adjustment card
Mains supply detection using an external contact
7. The KERYS saves your new configuration.
8. After return to the KERYS home screen,
The configuration will only be taken into account if the following operations are carried out:
Turn on the battery isolator switch.
Wait 5 seconds.
Turn off the battery isolator switch.
Important
Solo generating set, CRF coupling (A651)
1. Turn off the battery isolator switch.
2. Check that the emergency stop buttons are activated.
3. Press the “STOP” button of the KERYS.
4. Turn the changeover switch to position 4.
1: SOLO GENERATING SET WITHOUT GRID COUPLING
APPLICATION:
A612
2: PRODUCTION POWER PLANT WITHOUT GRID COUPLING
APPLICATION:
A632 / A633
3: NOT APPLICABLE
4 : SOLO GENERATING SET WITH GRID COUPLING
APPLICATION:
A651
(If the switch is already set to “
4”, turn the switch and return to position ‘’4’’)
Saving in flash …