Pre-Programmed Modes
11.2.4 How the Panel Works in Mode 2
Activation of either Z-1 or Z-2 turns NAC-1 on steady.
Activation of either Z-1 or Z-2 changes the Hazard Area 1 state from Idle into Alarm
directly. NAC-1 turns on steady. NAC-2 turns on Temporal. Release Timer-1 is started.
Expiration of Release Timer-1 activates both RAC-1 and RAC-2. NAC-1 and NAC-2 turn
on steady.
Activation of Z-6 starts Manual-release Timer 1 (MDT-1) in any situation. NAC-1 turns
on steady. NAC-2 turns on Temporal. Upon the expiration of MDT-1, RAC-1 and RAC-2
turn on.
During Hazard Alarm state, after Z-5 (abort switch) is pressed, Release Timer-1 will
reset and then restart. If Z-5 is held for any time up to 50 seconds, then the releasing
device will actuate 60 seconds after the switch is pressed. However, if Z-5 is held for
longer than 50 seconds, then the releasing device will actuate 10 seconds after the
switch is released.
Activation of Z-3 turns both NAC-1 and NAC-2 on steady.
Activation of Z-4 can be indicated on NAC-2 at 20BPM, if enabled.
11.3 Mode 3: Agent Release, Dual Hazard, Cross-zoned, Split
Release
This mode is no longer used.
11.4 Mode 4: Agent Release, Dual Hazard, Not Cross-zoned, Split
Release
This mode is no longer used.

Table of Contents

Other manuals for Secutron MR-2320 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Secutron MR-2320 Series and is the answer not in the manual?

Secutron MR-2320 Series Specifications

General IconGeneral
BrandSecutron
ModelMR-2320 Series
CategoryControl Panel
LanguageEnglish

Related product manuals