EasyManua.ls Logo

Secutron MR-2320 Series - Appendix D: Power Supply and Battery Calculations (Selection Guide)

Secutron MR-2320 Series
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
87
15.0 Appendix D: Power Supply and
Battery Calculations (Selection
Guide)
Use the form below to determine the required secondary power supply (batteries).
* Assume three Initiating Circuits are in alarm.
' Use 0.084 for five minutes, 0.168 for 10 minutes and 0.5 for 30 minutes of alarm as a multiplier figure.
Using the Mircom MPD-65P 2-wire photoelectric smoke detector. See LT-1007SEC Conventional Device Compatibility Guide for
other compatible smoke detectors.
Total Current Requirement: ALARM (B)______ Amps. (Value obtained from column B)
Battery Capacity Requirement:
Battery (AH) = ([STANDBY (A) ______ ] x [(24,60 or 90 Hours) ___ ]) +
([ALARM (B) ______ ] x [Alarm in Hr.] _____) = (C) ______AH
Total System Current in Alarm State: Must be 5.5 amperes or less for MR-2320 Series.
Battery Selection: Multiply (C) by 1.20 to derate battery.
IMPORTANT NOTICE
The main AC branch circuit connection for Fire Alarm Control Panel must provide a dedicated continuous power without provision of any
disconnect devices. Use #12 AWG wire with 600-volt insulation and proper over-current circuit protection that complies with the local codes.
Refer to Appendix C: Specifications on page 84 for specifications.
POWER REQUIREMENTS (ALL CURRENTS ARE IN AMPERES)
Model
Number
Description Qty Standby
Total
Standby
Alarm
Total
Alarm
MR-2320-R
Pre-Action/Deluge and
Agent Release Control
Panel FIXED ELR/ACTIVE
ELR
X 0.123/0.092
=
0.316/
0.292
=
MR-2300-A
Det Class A Converter
Adder Module
X0.000
= 0.000 =
MR-2300-NC2
Sig Class A Converter
Adder Module--2 Circuits
X0.000
= 0.000 =
MR-2300-PR
Polarity Reversal and City
Tie Module
X0.050
= 0.300 =
MR-2306-R6 6 Relay Adder Module X 0.000
= 0.080 =
MR-2312-S12
12 Relay Smart Relay
Module
X0.030
=0.140=
Two-Wire Smoke Detectors X 0.00011
= * 0.135 =
Four-Wire Smoke Detectors X
= =
Signal Load (bells, horns, strobes, and etc.) X
=
Auxiliary Power Supply for Annunciators, etc.
=
=
Total currents (Add above currents) STANDBY
(A)
ALARM
(B)

Table of Contents

Other manuals for Secutron MR-2320 Series

Related product manuals