Pre-Programmed Modes
11.13 Mode 13: Pre-action/deluge, Single Hazard, Not Cross Zoned,
Combined Release
11.13.1 Zone Configuration
Detection Zone -1: Alarm (Hazard Area 1, not cross-zoned)
Detection Zone -2: Alarm (Hazard Area 1, not cross-zoned)
Detection Zone -3: Alarm (Hazard Area 1, not cross-zoned)
Detection Zone -4: Supervisory
Detection Zone -5: Supervisory
Detection Zone -6: Water-flow.
NAC -1: Signal, steady on any alarm.
NAC -2: Escalating signal, indicates Hazard Area 1 status, Supervisory Optional.
RAC -1: Releasing Circuit (Hazard Area 1)
RAC -2: Releasing Circuit (Hazard Area 1)
11.13.2 Hazard Configuration
Default Release Timer Value: 0 seconds
Default Manual Release Delay: 0 seconds (not used)
Default Abort Delay Type: Standard UL (not used)
Default Soak Timer Value: 0 seconds (continuous)
11.13.3 NAC Configuration
Default Escalating NAC code of Hazard Area State:
Hazard Idle: Off
Hazard Alert: Temporal (see Table 8)
Hazard Alarm: Temporal (see Table 8)
Hazard Release: Steady
Default NAC code of Supervisory is 20 BPM.
Detection Zones Phantom Zones
Z1 Z2 Z3 Z4 Z5 Z6 Zp1
RT1
Exp
Alm Alm Alm Supv Supv WF Z1+Z2+Z3
Out1 Signal Steady XXX X
Out2 Signal Escalating (X) (X) X X
Out3 Rel. Releasing X
Out4 Rel. Releasing X
RLS TMR 1 Started XXX
RLS Tmr 1 Interrupted
RLS Tmr 1 Cancelled

Table of Contents

Other manuals for Secutron MR-2320 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Secutron MR-2320 Series and is the answer not in the manual?

Secutron MR-2320 Series Specifications

General IconGeneral
BrandSecutron
ModelMR-2320 Series
CategoryControl Panel
LanguageEnglish

Related product manuals