Pre-Programmed Modes
Hazard Release: Steady
Default NAC code of Supervisory is 20 BPM.
11.12.4 How the Panel Works in Mode 12
Activation of Z-1, Z-2 or Z-3 changes Hazard Area 1 state from Idle to Alert. NAC-1 turns
on steady. NAC-2 sounds Temporal.
Activations of any two of Z-1, Z-2 and Z-3 change Hazard Area 1 state into Alarm.
Release Timer-1 is started. NAC-2 turns on at 120 BPM. Upon the expiration of Release
Timer 1, both RAC-1 and RAC-2 turn on Steady. RAC-1 and RAC-2 are activated.
Activation of Z-6 turns on both NAC-1 and NAC-2 steady.
Activation of Z-4 or Z-5 is indicated on NAC-2 at 20 BPM, if configured.