65
Pre-Programmed Modes
11.6.4 How the Panel Works in Mode 6
• Activation of any one among Z-1, Z-2, Z-3 and Z-4 changes Hazard Area 1 state into
Alarm. Release Timer-1 is started. NAC-1 turns on at Temporal. Upon the expiration of
Release Timer-1, NAC-1 turns on steady. RAC-1 and RAC-2 are activated.
• Activation of Z-5 can be indicated on NAC-2 at 20 BPM, if configured.
• Activation of Z-6 turns NAC-1 steady.