Pre-Programmed Modes
Default NAC code of supervisory is Temporal (see Table 8)
11.10.4 How the Panel Works in Mode 10
Activation of either Z-1 or Z-2 turns NAC-1 on steady.
Activation of either Z-1 or Z-2 turns NAC-2 on at 60BPM. Release Timer-1 is started.
Expiration of Release Timer-1 activates both RAC-1 and RAC-2. NAC-1 and NAC-2 turn
on steady.
Activation of Z-6 starts Manual Release Delay Timer -1(MDT-1). Upon the expiration of
MDT-1, both RAC-1 and RAC-2 are active. NAC-1 and NAC-2 turn on steady.
If Z-5 is active, NAC-2 is downgraded from 60BPM to 20BPM. After releasing of Z-5,
NAC-2 goes back to 60BPM. Release Timer-1’s values depend on Abort Delay Type.
During Hazard Alarm state, after Z-5 (abort switch) is pressed, Release Timer-1 will
reset and then restart. If Z-5 is held for any time up to 50 seconds, then the releasing
device will actuate 60 seconds after the switch is pressed. However, if Z-5 is held for
longer than 50 seconds, then the releasing device will actuate 10 seconds after the
switch is released.
Activation of Z-3 turns both NAC-1 and NAC-2 on steady.
Activation of Z-4 can be indicated on NAC-2 at Temporal, if configured.

Table of Contents

Other manuals for Secutron MR-2320 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Secutron MR-2320 Series and is the answer not in the manual?

Secutron MR-2320 Series Specifications

General IconGeneral
BrandSecutron
ModelMR-2320 Series
CategoryControl Panel
LanguageEnglish

Related product manuals