Pre-Programmed Modes
Default NAC code of supervisory is 20 BPM
11.11.4 How the Panel Works in Mode 11
The activation of either Z-1 or Z-2 turns NAC-1 on steady.
The activations of both Z-1 and Z-2 turn NAC-1 off and turn NAC-2 on at 60BPM.
Release Timer-1 is started.
Expiration of Release Timer-1 results in the activation of RAC-1 and RAC-2. NAC-2
turns on steady.
If Z-5 is active, NAC-2 turns off and NAC-1 turns on instead. After releasing of Z-5, NAC-
1 turns off and NAC-2 turns on at 60BPM. Release Timer-1’s values depend on Abort
Delay Type.
During Hazard Alarm state, after Z-5 (abort switch) is pressed, Release Timer-1 will
reset and then restart. If Z-5 is held for any time up to 50 seconds, then the releasing
device will actuate 60 seconds after the switch is pressed. However, if Z-5 is held for
longer than 50 seconds, then the releasing device will actuate 10 seconds after the
switch is released.
Activation of Z-6 starts Manual Release Delay Timer-1(MDT-1). Upon the expiration of
MDT-1, RAC-1 and RAC-2 are active. NAC-2 turns on steady.
Activation of Z-3 turns NAC-2 on steady.
Activation of Z-4 can be indicated on NAC-2 at 20BPM, if configured.