General Pickup, General Alarm, General Trip
wiProtGeneral_Y01
name = Each trip of an active, trip authorized protection module will lead to a general trip.
IL2
IL1
IL3
≥1
50
Prot . Alarm
≥1
51
Prot . Trip
IG
External Signals
52
Prot . TripCmd
49
Prot . Pickup
&
&
&
Example Protection Element
&
name . Pickup
20
21
t
name .
t
0
Φ
&
&
Protection Settings
19
Trip
name .
Definition
Alarm
2
(Stage is not deactivated and no active blocking signals)
name . Alarm
â—„
name . Trip
â—„
Other Protection Elements
20
Alarm
from other modules
21
Trip
from other modules
Prot .
Force Trip Cmd
Trip Cmd via SCADA
≥1
&
Prot . ExBlo TripCmd
≥1
18
Prot . Active
Fig. 39:
Rough sketch of the functionality of an example protection stage named »name«.
The diagram visualizes the protection signals of any WIC1 protection stage, »name«, and
how these are reported to the»Prot« master module. However, the phase-speci󰊟c signals
and the collective signals »Prot . Pickup I Ph« and »Prot . Pickup IG« have been omitted to
make the concept better understandable.
123WIC1WIC1-1.0-EN-MAN
4 Protective Elements
4.1.1 General Pickup, General Alarm, General Trip