4.7.2
Settings via DiggiMEC or via Smart view
1. ▷
Activate the protection stage and select whether it shall operate as a supervision or a
protection function, see ╚═▷ “4.1 »Prot« – General Protection Module”.
2. ▷
Select the Characteristic:
[Protection Para / I2>] »I2> . Char« =
Options:
“DEFT” (DEFinite-Time),
or any of the Inverse-time characteristics listed in ╚═▷ “11.2.3
Characteristics »I2>«”.
3. ▷
Specify the pickup threshold:
[Protection Para / I2>] »I2> . I2 — as a number value in units of the nominal current
In.
4. ▷
Only in case of the De󰊟nite-Time characteristic »I2> . Char« = “DEFT”:
Specify the tripping delay (in seconds):
[Protection Para / I2>] I2> . t«
5. ▷
Only in case of an Inverse-Time characteristic, select the Reset Mode, that controls the
reset delay:
[Protection Para / I2>] »I2> . Reset Mode« =
Options:
“instantaneous” (immediate reset),
“de󰊟nite time” (reset delay 󰊟xed to a particular time in seconds),
“inverse time” (reset delay depends on the selected characteristic. This option
is not available for some curves, see ╚═▷ “11.2.3 Characteristics »I2>«”.)
6. ▷
Only in case of an Inverse-Time characteristic with 󰊟xed reset delay, »I2> . Reset
Mode« = “de󰊟nite time”:
Specify the reset delay (in seconds):
[Protection Para / I2>] »I2> . tReset«
(Remark: For the De󰊟nite-Time overcurrent, the reset delay always equals 0.)
7. ▷
Only in case of an Inverse-Time characteristic:
Specify the minimum trip delay (in seconds, see ╚═▷ “Explanation for All
Characteristics (»I2>«)” for details):
[Protection Para / I2>] »I2> . tMin«
8. ▷
Only in case of an Inverse-Time characteristic:
Specify the tripping characteristic factor (see ╚═▷ “Explanation for All
Characteristics (»I2>«)” for details):
[Protection Para / I2>] »I2> . tChar«
158 WIC1 WIC1-1.0-EN-MAN
4 Protective Elements
4.7.2 Settings via DiggiMEC or via Smart view