EasyManuals Logo

Seg WIC1 User Manual

Seg WIC1
337 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #159 background imageLoading...
Page #159 background image
9. ▷
If Inrush Blocking has been activated (see ╚═▷ “4.4 IH2 - Inrush Blocking”), select
whether this Earth (Ground) Overcurrent stage shall be blocked in case of an inrush
current:
[Protection Para / I2>] »IH2 Blo« =
Options:
“Inactive” (no Inrush blocking of the ground overcurrent protection),
Active” (the Inrush Blocking module also blocks the ground overcurrent
protection).
159WIC1WIC1-1.0-EN-MAN
4 Protective Elements
4.7.2 Settings via DiggiMEC or via Smart view

Table of Contents

Other manuals for Seg WIC1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Seg WIC1 and is the answer not in the manual?

Seg WIC1 Specifications

General IconGeneral
BrandSeg
ModelWIC1
CategoryRelays
LanguageEnglish

Related product manuals