11.2 Appendix – Time Overcurrent Characteristics
11.2.1
Characteristics (I>, I>>, I>>>)
For each phase overcurrent stage, the following characteristics are available:
DEFTDe󰅰nite Time-Overcurrent
Inverse-Time Overcurrent Curves according to IEC 60255‑151:
NINVIEC Normal Inverse (IEC 60255‑151)
VINVIEC Very Inverse (IEC 60255‑151)
LINVIEC Long Time Inverse (IEC 60255‑151)
EINVIEC Extremely Inverse (IEC 60255‑151)
RINVR Inverse
HV Fuse Fuse Characteristic of an HV Fuse
FR Fuse Fuse Characteristic of a Full Range Fuse
Curves De󰊟ned in IEEE C37.112:
MINVIEEE Moderately Inverse (IEEE C37.112)
VINVIEEE Very Inverse (IEEE C37.112)
EINVIEEE Extremely Inverse (IEEE C37.112)
EF Curve “EF” Curve
Explanation for All Characteristics (I>, I>>, I>>>)
(Remark: All settings are given for protection stage »I>«. »I>>« and »I>>>« have the
same settings with corresponding menu branches.)
I: Fault current
I> = I
>
: Pickup value for the Phase Overcurrent stage. If the pickup value is
exceeded, the stage starts to time out to trip.
Setting: [Protection Para / I>] »I«
Trip delay t for I > I
>
:
for »Char« = “DEFT”: settable via [Protection Para / I>] »t«.
for all other characteristics: calculated based on the selected curve.
Reset mode for I < I
>
, settable via »Reset Mode«, available options:
With option »Reset Mode« = “instantaneous”: Instantaneous reset: when the
current drops below the pickup setting, the TOC time resets to zero within 2
cycles.
With option »Reset Mode« = “de󰊟nite time”: The reset delay is settable
at »tReset«.