10.2.3
Self-Supervision – Information Messages
Description Information Corrective Action
SI 1 Firmware Update Information that a new device
󰅰rmware has been installed on
the WIC1. The displayed “Value”
is the new Build number after the
update.
SI 2 Device restart Information that the WIC1 has
been restarted.
The displayed “Value” shows the reason
for the device restart. See the table in
╚═▷ “6.1 Device Start (Reboot)”.
However, the restart reasons number 1
and 6 are intentionally omitted, i. e. get
never listed as SI 2 messages.
SI 3 Settings changed Information that the settings (e.g.
the protection parameters) have
been modi󰅰ed.
The message value is a counter
value. Each change of the settings –
independent of the number of changed
parameters – increases this counter by
1.
This is also true of settings that are
made via DIP/HEX switches.
SI 4 DiggiMEC Restart Reason Information that the DiggiMEC has
been restarted.
The displayed “Value” shows the reason
for the device restart. See the table in
╚═▷ “6.1 Device Start (Reboot)”.
However, the restart reasons number 1
and 6 are intentionally omitted, i. e. get
never listed as SI 4 messages.
SI 5 DiggiMEC HMI Issue Information about communication
problems between WIC1 and the
DiggiMEC HMI.
The message value is a counter value.
Each failure of data transfer between
WIC1 and DiggiMEC increases this
counter by 1.
Note that the 󰊠ag indicators / output
relays are not a󰊞ected.