[Protection Para / I>] »I> . tChar«
9. ▷
If Inrush Blocking has been activated (see ╚═▷ “4.4 IH2 - Inrush Blocking”), select
whether this Earth (Ground) Overcurrent stage shall be blocked in case of an inrush
current:
[Protection Para / I>] »IH2 Blo« =
Options:
“Inactive” (no Inrush blocking of the ground overcurrent protection),
Active” (the Inrush Blocking module also blocks the ground overcurrent
protection).
143WIC1WIC1-1.0-EN-MAN
4 Protective Elements
4.3.2.1 Phase Overcurrent Protection – Settings via DiggiMEC or via Smart view