EasyManua.ls Logo

SEW-Eurodrive DFE24B EtherCAT - Velocity Mode Settings; Position Mode Settings

SEW-Eurodrive DFE24B EtherCAT
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
76
Manual – Fieldbus Interface DFE24B EtherCA
8
EtherCAT
®
master settings
Motion Control via EtherCAT
®
8.3.1 Velocity mode settings
The speed setpoint is written directly to system variable H499 via the configured
PDO2 and is scaled as follows:
–1 digit 0.2 rpm, that is, a value of 5000 rpm
The parameters used in the controller must be scaled before they are transferred to
the inverter.
The control word is transferred via PDO1 together with the speed setpoint in PDO2.
The position that is transferred to the controller is read directly from system variable
H511 via the configurable PDO2. The position is scaled as follows:
4096 digits represent one revolution
The position that is read in must then be scaled to the parameters used in the con-
troller.
The status word is transferred via PI1 together with the actual position value in
PDO2.
8.3.2 Position mode settings
The position setpoint is written directly to system variable H499 via the configured
PDO2 and is scaled as follows:
1 motor revolution 2
16
The parameters used in the controller must be scaled accordingly before they are
transferred to the inverter.
The control word can be transferred as follows:
Via PO1 together with the position setpoint in PDO2
Directly to a system variable in IPOS
plus®
if the status machine has to be opti-
mized. The application-specific adjustment of the status machine is then exe-
cuted as an IPOS
plus®
program or as a PLC program in the motion controller.
The position that is transferred to the controller is read directly from system variable
H508 via the configurable PDO2. The position is scaled as follows:
1 motor revolution 2
16
The position that is read in must then be scaled to the parameters used in the con-
troller.
The status word can either be transferred via PI1 together with the position setpoint
in PDO2, or - if the status machine is adapted for a particular application in IPOS
plus®
- read in directly from a system variable in IPOS
plus®
.
00
I

Table of Contents

Related product manuals